For
air line protection, Van Air RD Series refrigerated compressed
air dryers combine the newest technology in heat transfer
with a proven refrigeration system to keep your pneumatic
equipment running at peak efficiency. Providing a constant
35 - 38° F dew point and low initial cost, an RD Series
refrigerated air dryer provides the best combination of performance
and economy.
All
the components of an RD Series refrigerated compressed air
dry are housed in a powder coated cabinet to ensure a long
useful life. All units include CFC-free R-22 refrigerant,
a refrigerant analyzer light, non-cycling refrigerant compressors,
a compressor run light, and a built-in drain.
A capacity
control valve allows the dryer to operate efficiently at
low loads by preventing heat exchanger freeze-ups. The control
valve also keeps the dew point steady when the air flow
changes. For maximum performance, it is recommended that
a pre-filter be installed.
| Advantages
of the RD Air Dryer |
•
Immediate Availability for Standard Models
•
Extensive Variety of Sizes from 10 to 3,000 SCFM
•
Shell and Tube Heat Exchangers for Maximum Performance and
Low Pressure Drop
•
No Heat Exchanger Freeze-Ups with Low Loads
•
160°
F maximum Inlet Temperature
• Effective Moisture Removal for Indoor Air Systems
For
indoor air line protection, RD Series refrigerated compressed
air dryers keep your pneumatic equipment running at peak
efficiency with a constant 35-38° F dew point.
• Low-Load Protection
A
capacity control valve allows the dryer to operate efficiently
at low loads by preventing heat exchanger freeze-ups. It
also keeps the dew point steady when the flow changes.
Dimensions
and Specifications - SCFM, Inches and Pounds |
| |
| Model
|
Stand.
Cap. |
A |
B |
C |
In
/ Out |
Comp
HP |
Comp
KW |
Weight
|
|
RD-10 |
10 |
14 |
15 |
18 |
1/2
NPT |
1/6
|
.29 |
69 |
|
RD-20 |
20 |
14 |
15 |
18 |
1/2
NPT |
1/5
|
.36 |
78 |
|
RD-30 |
30 |
23 |
14 |
34 |
3/4
NPT |
1/4
|
.45 |
140 |
|
RD-40 |
40 |
23 |
14 |
34 |
1 NPT |
1/3
|
.58 |
160 |
|
RD-60 |
60 |
23 |
14 |
34 |
1 NPT |
1/2
|
.86 |
176 |
|
RD-80 |
80 |
32 |
20 |
35 |
1 NPT |
1/2
|
.86 |
200 |
|
RD-100 |
100 |
32 |
20 |
35 |
1 NPT |
3/4
|
1.2 |
256 |
|
RD-130 |
130 |
32 |
20 |
35 |
1 1/2 NPT |
3/4
|
1.2 |
258 |
|
RD-150 |
150 |
32 |
20 |
35 |
1 1/2 NPT |
3/4
|
1.2 |
270 |
|
RD-220 |
220 |
38 |
22 |
47 |
2 NPT |
1 |
1.75 |
390 |
|
RD-250 |
250 |
38 |
22 |
47 |
2 NPT |
1 1/2 |
2.63 |
418 |
|
RD-330 |
330 |
52 |
28 |
55 |
2 NPT |
1 1/2 |
2.63 |
700 |
|
RD-400 |
400 |
52 |
28 |
55 |
2 1/2 NPT |
2 |
3.5 |
925 |
|
RD-500 |
500 |
52 |
28 |
55 |
2 1/2 NPT |
3 |
5.25 |
968 |
|
RD-650 |
650 |
52 |
28 |
55 |
2 1/2 NPT |
3 |
5.25 |
982 |
|
RD-800 |
800 |
61 |
41 |
74 |
3 FLG |
4 |
7 |
1620 |
|
RD-1000 |
1000 |
61 |
41 |
74 |
3 FLG |
5 |
8.75 |
1754 |
|
RD-1200 |
1200 |
61 |
41 |
74 |
3 FLG |
5 |
8.75 |
1860 |
|
RD-1500 |
1500 |
62 |
48 |
78 |
4 FLG |
7 1/2 |
13.13 |
2365 |
|
RD-2000 |
2000 |
67 |
54 |
102 |
6 FLG |
10 |
17.5 |
3150 |
|
RD-2500 |
2500 |
67 |
54 |
102 |
6 FLG |
15 |
26.25 |
3370 |
|
RD-3000 |
3000 |
77 |
66 |
108 |
6 FLG |
15 |
26.25 |
4015 |
|
| |
| Correction
Factors
If
operating conditions vary from the standard 100 PSIG,
100° F inlet temperature and 100° F ambient,
use the correction factors against the standard flow. |
Inlet
Temperature |
Correction
Factor |
| 90° |
.85 |
| 100° |
1.00 |
| 110° |
1.15 |
| 120° |
1.30 |
| 140° |
1.70 |
| 160° |
1.90 |
|
Working
Pressure |
Correction
Factor |
| 50 |
1.25 |
| 75 |
1.11 |
| 90 |
1.05 |
| 100 |
1.00 |
| 110 |
.99 |
| 125 |
.98 |
| 150 |
.95 |
|
Ambient
Temperature |
Correction
Factor |
| 90° |
.95 |
| 100° |
1.00 |
| 110° |
1.10 |
|
| Example
625
SCFM at 120° F inlet temperature, 125 PSIG and
110° F ambient.
625 x 1.3 x .98 x 1.1 = 876 SCFM
Use Model RD-1000

|